3.4 Replacing a defective slave (without teach-in of actuator)
If an AS-i safety slave is defective, it can be replaced even without a PC or reconfiguration of
the AS-i Safety Monitor by pressing the ESC/Service key on the AS-i Safety Monitor.
All safety slaves without necessity for teach-in of an actuator can be replaced without using a
PC with ASiMon according to this method.
Proceed as follows:
1. Disconnect defective slave from AS-i bus.
2. Press the ESC/Service button on the AS-i Safety Monitor approx. 3 seconds.
3. Connect new slave with address 0 AND bring into safe state
The monitor addresses this slave automatically
4. Press the ESC/Service button on the AS-i Safety Monitor approx. 3 seconds.
The code table for the new slave is taught and checked for correctness. If this is OK,
the AS-i Safety Monitor changes to protecting mode.
SLAVE 6 TO
BE CONNECTED
THEN PRESS
SERVICE LONG