Operating Instructions Safety System CES-AZ-AES-...
38
Read head CES-A-LMN-SC
Ì Cylindrical design M12
Ì M8 plug connector (snap-action and screw terminals)
Dimension drawing
Note
The read head is allowed to be installed as a maximum up to the clear zone (area
of the active face without metal housing).
Typical operating distance
With evaluation unit CES-AZ-AES-... and actuator CES-A-BMB
Note
A minimum distance of s = 1.2 mm must be maintained.
Approvals
17
5
32
19,7
s
m
35
4
8
30
M12x1
M8x1
37
1)
1)
Reading distance
Centre offset
connected
Active face
1) Clear zone (area of the active face without metal housing)